Certified Fire Protection Specialist (CFPS) — Question 5
In assessing the use of a sprinkler head with a Nominal K-Factor of 14.0, you find that this sprinkler head provides what percentage of the flow from a Nominal K-Factor 5.6 sprinkler device?
Answer options
- A. 100%
- B. 140%
- C. 250%
- D. 300%
Correct answer: D
Explanation
The correct answer is D, 300%, because the flow rate of a sprinkler is proportional to the square of its K-Factor. Therefore, (14.0^2) / (5.6^2) equals 300%. The other options are incorrect as they do not reflect the correct ratio of the flow rates based on the K-Factors provided.