Troubleshooting Cisco Data Center Infrastructure (DCIT) — Question 5

A Cisco ACI environment consists of three Cisco APICs, two spine switches, and four leaf switches. The engineer erases and reboots all APICs first, then leaf and spine switches individually, and then completes the Initial Setup dialog on the APIC1 CIMC KVM console. When the engineer logs in to the APIC1 web GUI, the engineer notices that there are no directly connected leaf switches being discovered under Fabric > Inventory > Fabric Membership. What is the cause of the issue?

Answer options

Correct answer: C

Explanation

The correct answer is C because failing to enter the TEP Pool value during the Initial Setup prevents the APIC from establishing proper communication with the leaf switches. Option A is incorrect as it implies an improper reset that doesn't relate to the TEP Pool configuration. Option B is wrong since rebooting is part of the setup process. Option D is not relevant in this context, as the Fabric Name does not affect TEP Pool discovery.